1-CSKH-V180 P15-R - P60-R, PH120-R, P75090-R, PS15 - PS60, B2ca s1a d1 a1 SiR/FRNC energy cables, with circuit integrity, UV resistant, Water resistant

Safety Cables with circuit integrity

Cables are designed for fixed distribution of electricity in buildings with a high concentration of people to protect them and protect the technical equipment of buildings in the event of fire, where there is no requirement to maintain the functionality of the cable installation in fire. In case of fire, the cable releases a small amount of heat and smoke. The cables are resistant to UV radiation and water AD1-AD7.

Design

This product consists of:

  • 1
    Copper conductor, round fine stranded (RF)
  • 2
    Core insulation (Silicone rubber)
  • 3
    Inner covering (halogen-free filling compound)
  • 4
    Sheath (halogen-free polymer compound, brown, UV resistant, Water resistant)

Technical Data

Standard: 
  • ČSN 34 7660-100
  • TP PRAKAB 01/21
Certificate: 
  • EZÚ Czech Republic
  • TSÚS Slovakia
Test Voltage: core/core 4 kV / 50 Hz
Rated Voltage: 0,6/1 kV
Bending radius (min.): 
  • 12 x Ø of cable (multicore)
  • 15 x Ø of cable (singlecore)
Fire properties: 
  • ČSN EN 60332-1-2: self-extinguishing
  • ČSN EN 60754-2: halogen-free, non-corrosive combustion gases
  • ČSN EN 61034-2: low smoke emission
  • ČSN EN 60332-3-22: reduced flame propagation
  • ČSN 73 0895, STN 92 0205: circuit integrity
  • ČSN EN 13501-6: fire classification
  • CPR Classification: B2ca s1a d1 a1
Core identification: 
  • ČSN 33 0166 ed. 2
  • ČSN EN 50334
Temperature range: 
  • Laying temperature: min. -5°C
  • Operating temperature: -50°C up to 60°C
  • Conductor temperature: max. 90°C
  • Short circuit temperature: max. 250°C
Cable image - PRAFlaDur+ T
+
-
Cable image - PRAFlaDur+ T
+
-
Cable image - PRAFlaDur+ T
+
-

Contact us

Are you interested in this product?

Jan Pietroň

Product supervisor

+420 604 471 907
[email protected]

Options

Add to inquiry
Number of cores x nominal cross-section (mm²)
Max. conductor resistance (Ω/km)
Current rating in the earth (A)
Current rating in the air (A)
Outer diameter appr. (mm)
Total weight appr. (kg/km)
2 x 1.5 RF
13.3
45
29
10.5
151
3 x 1.5 RF
13.3
39
24
11.1
171
4 x 1.5 RF
13.3
39
24
12.0
198
5 x 1.5 RF
13.3
39
24
13.2
235
3 x 2.5 RF
7.98
51
32
12.3
222
4 x 2.5 RF
7.98
51
32
13.3
261
5 x 2.5 RF
7.98
51
32
14.4
303
3 x 4 RF
4.95
66
42
14.2
314
4 x 4 RF
4.95
66
42
15.4
373
5 x 4 RF
4.95
66
42
16.8
438
3 x 6 RF
3.3
82
53
14.7
340
4 x 6 RF
3.3
82
53
15.9
411
5 x 6 RF
3.3
82
53
19.2
590
4 x 10 RF
1.91
110
74
20.3
732
5 x 10 RF
1.91
110
74
22.4
890
4 x 16 RF
1.21
142
98
22.9
1017
5 x 16 RF
1.21
142
98
26.3
1310

Technical changes reserved.

All figures are therefore without guarantee.

To inquiry

Check other recommended products by SKB Group

Safety Cables with circuit integrity

Browse products
Safety Cables with circuit integrity
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Low Voltage Cables 0,6/1 kV
Medium Voltage Cables up to 36 kV
Automation and Motor Supply Cables
Railway Signalling and Telecommunications Cables