Cu
Prakab (Czech market)
Validity: CW 46/2025
Cu
Quotation
Kč / kg:186.69
Prakab (Slovak market)
Validity: CW 46/2025
Cu
Quotation
€ / kg:7.72

All statements without guarantee.

Al
Prakab (Czech market)
Validity: CW 46/2025
Al
Quotation
Kč / kg:55.21
Prakab (Slovak market)
Validity: CW 46/2025
Al
Quotation
€ / kg:2.29

All statements without guarantee.

Customer Portal

Cables

6-CYKCY

Download PDF

Add to inquiry

Download PDF

To inquiry

PVC/PVC copper underground medium voltage cable, screened

Medium Voltage Cables up to 36 kV

The cables are designed for fixed distribution of electricity in the ground or in the outdoor environment.

Design

This product consists of:

  • 1
    Copper conductor, round stranded (RM) resp. sector-shaped stranded (SM)
  • 2
    Core insulation (PVC)
  • 3
    Inner covering (EPDM or plastic tape)
  • 4
    Inner sheath (PVC colorless)
  • 5
    Screen (copper tape or bare copper wires applied with changing direction of lay)
  • 6
    Inner covering (plastic tape)
  • 7
    Sheath (PVC black, UV-resistant)

Technical Data

Standard: TP PRAKAB 03/08
Certificate: EZÚ Czech Republic
Test Voltage: 15 kV / 50 Hz
Rated Voltage: 3,6/6 kV
Bending radius (min.): 
  • 6 x Ø of cable up to 20 mm
  • 12 x Ø of cable from 20 mm to 40 mm
  • 15 x Ø of cable over 40 mm
Fire properties: 
  • ČSN EN 60332-1-2: self-extinguishing
  • CPR classification: Eca
Core identification: Natural cores colour
Temperature range: 
  • Laying temperature: min. -5°C
  • Operating temperature: -50°C up to 70°C
  • Conductor temperature: max. 70°C
  • Short circuit temperature: max. 140°C
Cable image - 6-CYKCY
+
-
Cable image - 6-CYKCY
+
-
Cable image - 6-CYKCY
+
-

Contact us

Are you interested in this product?

Ing. Dan Bachtík

Product supervisor

+420734366090
[email protected]

Options

Add to inquiry
Number of cores x nominal cross-section / cross-section of screen (mm²)
Number of cores x nominal cross-section / cross-section of screen (mm²)
Max. conductor resistance (Ω/km)
Current rating in the earth (A)
Current rating in the air (A)
Outer diameter appr. (mm)
Total weight appr. (kg/km)
3 x 25 RM / 16
0.727
88
71
37
2352
3 x 35 RM / 16
0.524
118
99
39.1
2755
3 x 50 RM / 16
0.387
143
119
42.1
3338
3 x 70 SM / 16
0.268
176
150
41.5
3171
3 x 70 SM / 50
0.268
176
150
44.1
3477
1 x 95 RM / 16
0.193
252
250
28.2
1659
1 x 95 RM / 25
0.193
252
250
29.6
1762
3 x 95 SM / 16
0.193
211
182
45
4101
1 x 120 RM / 25
0.153
286
290
30.9
2021
3 x 120 SM / 25
0.153
240
210
48.9
4991
1 x 150 RM / 25
0.124
314
327
32.4
2315
3 x 150 SM / 16
0.124
269
238
50.2
5747
3 x 150 SM / 25
0.124
269
238
51.7
5861
1 x 185 RM / 25
0.0991
354
376
32.8
2789
3 x 185 SM / 16
0.0991
305
273
52.9
6893
3 x 185 SM / 25
0.0991
305
273
54.4
6999
1 x 240 RM / 25
0.0754
406
443
36.5
3278
3 x 240 SM / 25
0.0754
354
323
58.4
8711
1 x 300 RM / 25
0.0601
452
503
38.7
3888
1 x 400 RM / 25
0.047
499
573
41.9
4729
1 x 500 RM / 35
0.0366
560
659
46.1
5888

Technical changes reserved.

All figures are therefore without guarantee.

To inquiry

Check other recommended products by SKB Group

Medium Voltage Cables up to 36 kV

Browse products
Medium Voltage Cables up to 36 kV
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Low Voltage Cables 0,6/1 kV
Safety Cables with circuit integrity
Rubber, Silicone and PUR Cables
Commercial Vehicles and EVC Cables
Automation and Motor Supply Cables
Railway Signalling and Telecommunications Cables
Special Cables
Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.

Let's work
together

KONEKA

Discover

SKB Group

KONEKA logo

KONEKA s.r.o.

Ke Kablu 278, 102 00 Praha 10 · Hostivař

  • +420 272 070 210

  • [email protected]

  • Compliance

  • Privacy Policy

All rights reserved. Copyright © 2025