Koneka
SKB
Prakab
SKW
ICS
IKK

Menu

KONEKA logo
Cu
Prakab (Czech market)
Validity: CW 46/2025
Cu
Quotation
Kč / kg:186.69
Prakab (Slovak market)
Validity: CW 46/2025
Cu
Quotation
€ / kg:7.72

All statements without guarantee.

Al
Prakab (Czech market)
Validity: CW 46/2025
Al
Quotation
Kč / kg:55.21
Prakab (Slovak market)
Validity: CW 46/2025
Al
Quotation
€ / kg:2.29

All statements without guarantee.

Customer Portal

Cables

PRAFlaSafe +T

Download PDF

Add to inquiry

Download PDF

To inquiry

1-CSKH-R B2ca s1a d1 a1 SiR/FRNC copper energy cables, without insulation integrity and class 5 cores

Low Voltage Cables 0,6/1 kV

Cables are designed for fixed distribution of electricity in buildings with a high concentration of people to protect them and protect the technical equipment of buildings in the event of fire, where there is no requirement to maintain the functionality of the cable installation in fire. In case of fire, the cable releases a small amount of heat and smoke. The cables are resistant to UV radiation and water AD1-AD7.

Design

This product consists of:

  • 1
    Copper conductor (RF, class 5 acc. EN60228)
  • 2
    Core insulation (silicone rubber)
  • 3
    Inner covering (halogen-free filling compound)
  • 4
    Sheath (halogen-free polymer compound, orange, UV-resistant, water resistant)

Technical Data

Standard: 
  • ČSN 34 7660-100
  • TP PRAKAB 01/21
Certificate: EZÚ Czech Republic
Test Voltage: core/core 4 kV / 50 Hz
Rated Voltage: 0,6/1 kV
Bending radius (min.): 
  • 12 x Ø of cable (multicore)
  • 15 x Ø of cable (singlecore)
Fire properties: 
  • ČSN EN 60332-1-2: self-extinguishing
  • ČSN EN 60754-2: halogen-free, non-corrosive combustion gases
  • ČSN EN 61034-2: low smoke emission
  • ČSN EN 60332-3-22: reduced flame propagation
  • ČSN EN 13501-6: fire classification
  • CPR Classification: B2ca s1a d1 a1
Core identification: HD 308 S2
Temperature range: 
  • Laying temperature: min. -5°C
  • Operating temperature: -40°C up to 60°C
  • Conductor temperature: max. 90°C
  • Short circuit temperature: max. 90°C
Cable image - PRAFlaSafe +T
+
-
Cable image - PRAFlaSafe +T
+
-
Cable image - PRAFlaSafe +T
+
-

Contact us

Are you interested in this product?

Ing. Dan Bachtík

Product supervisor

+420734366090
[email protected]

Options

Add to inquiry
Number of cores x nominal cross-section (mm²)
Max. conductor resistance (Ω/km)
Current rating in the earth (A)
Current rating in the air (A)
Outer diameter appr. (mm)
Total weight appr. (kg/km)
3 x 1.5 RF
13.3
39
24
11.1
171
4 x 1.5 RF
13.3
39
24
12
198
5 x 1.5 RF
13.3
39
24
13
229
3 x 2.5 RF
7.98
51
32
12.3
222
5 x 2.5 RF
7.98
51
32
14.4
303
5 x 4 RF
4.95
66
42
16.8
438
5 x 6 RF
3.3
82
53
19.2
590
5 x 10 RF
1.91
110
74
22.4
890
5 x 16 RF
1.21
142
98
26.3
1310

Technical changes reserved.

All figures are therefore without guarantee.

To inquiry

Check other recommended products by SKB Group

Low Voltage Cables 0,6/1 kV

Browse products
Low Voltage Cables 0,6/1 kV
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Safety Cables with circuit integrity
Medium Voltage Cables up to 36 kV
Rubber, Silicone and PUR Cables
Commercial Vehicles and EVC Cables
Automation and Motor Supply Cables
Railway Signalling and Telecommunications Cables
Special Cables
Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.

Let's work
together

KONEKA

Discover

SKB Group

KONEKA logo

KONEKA s.r.o.

Ke Kablu 278, 102 00 Praha 10 · Hostivař

  • +420 272 070 210

  • [email protected]

  • Compliance

  • Privacy Policy

All rights reserved. Copyright © 2025